Assessment Year 2026
Principal Product Conveyor and Conveying Equipment
NAICS 333922: Conveyor and Conveying Equipment Manufacturing
SIC 3535: Conveyors and Conveying Equipment
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 87,000
ft2
Annual Production 5,000
units
Production Hrs. Annual 8,760
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $66,677 961,948
kWh
Electricity Demand $44,349 2,788
kW-mo/yr
Electricity Fees $8,338 -
Natural Gas $28,087 3,912
MMBtu
Waste Disposal Costs
Water Usage $8,628 243
Tgal
TOTAL YEARLY COSTS $156,079
RECOMMENDED SAVINGS* $150,108 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Primary Raw Material Savings
01 2.4221: Install compressor air intakes in coolest locations $1,251 $780 $950
13,764
kWh
$301
-
kW-mo/yr
- -
02 2.9114: Use solar heat to make electricty $134,142 $691,579 $89,785
1,301,226
kWh
$44,357
-
kW-mo/yr
- -
03 4.212: Adopt in-house material generation $7,821 $66,659 $(-2,440.1)
(-35,364)
kWh
$(-1,204.4)
-
kW-mo/yr
- $11,466
04 2.4322: Use or replace with energy efficient substitutes $2,474 $2,300 $1,644
23,820
kWh
$830
-
kW-mo/yr
- -
05 2.4322: Use or replace with energy efficient substitutes $3,074 $950 $2,364
34,260
kWh
$710
-
kW-mo/yr
- -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $525 $288 $404
5,847
kWh
$121
-
kW-mo/yr
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $822 $400 $624
9,044
kWh
$202
-
kW-mo/yr
$(-4.7)
-
MMBtu
-
TOTAL RECOMMENDED $150,108 $762,956 $93,330
1,352,597
kWh
$45,317
-
kW-mo/yr
$(-4.7)
-
MMBtu
$11,466
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Primary Raw Material Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs