| Assessment Year | 2025 |
|---|---|
| Principal Product | HDPE rigid plastic containers |
| NAICS | 326160: Plastics Bottle Manufacturing |
| SIC | 3085: Plastics Bottles |
| Sales Range | $10 M to 50M |
| # of Employees | 48 |
| Plant Area |
200,000
ft2
|
| Annual Production | 35,000,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $181,624 | 7,465,113 |
kWh
|
$0.024 | |
| Electricity Demand | $206,749 | 18,979 |
kW-mo/yr
|
$10.89 | |
| Electricity Fees | $41,815 | - |
|
- | |
| Natural Gas | $40,381 | 4,981 |
MMBtu
|
$8.11 | |
| Waste Disposal Costs | |||||
| Water Usage | $5,343 | 7,655 |
Tgal
|
$0.70 | |
| TOTAL YEARLY COSTS | $475,912 | ||||
| RECOMMENDED SAVINGS* | $36,172 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7241: Install outside air damper / economizer on hvac unit | $9,345 | $13,327 |
$6,120
254,987
kWh
|
$3,225
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $440 | - |
$241
10,032
kWh
|
$200
-
kW-mo/yr
|
- | |
| 03 | 2.4239: Eliminate or reduce compressed air usage | $2,821 | $4,859 |
$2,763
115,128
kWh
|
$58
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,819 | $678 |
$2,039
84,959
kWh
|
$1,780
-
kW-mo/yr
|
- | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $393 | $1,089 |
$389
16,216
kWh
|
$4
-
kW-mo/yr
|
- | |
| 06 | 2.3191: Use demand controller or load shedder | $657 | $3,632 |
$170
7,080
kWh
|
- |
$487
-
MMBtu
|
|
| 07 | 2.2511: Insulate bare equipment | $2,266 | $2,982 |
$1,210
50,414
kWh
|
$1,056
-
kW-mo/yr
|
- | |
| 08 | 2.2628: Utilize a less expensive cooling method | $15,398 | $114,881 |
$8,221
342,550
kWh
|
$7,176
-
kW-mo/yr
|
- | |
| 09 | 2.3132: Recharge batteries on during off-peak demand periods | $941 | - | - |
$941
-
kW-mo/yr
|
- | |
| 10 | 2.7221: Lower temperature during the winter season and vice-versa | $93 | - |
$50
2,067
kWh
|
$43
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $36,172 | $141,447 |
$21,203
883,434
kWh
|
$14,483
-
kW-mo/yr
|
$487
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs