Assessment Year | 2024 |
---|---|
Principal Product | Color systems, color cards, fan decks and color samples for the decorative paint market |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 3999: Manufacturing Industries, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
333,000
ft2
|
Annual Production | 100,000
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $115,993 | 2,025,253 |
kWh
|
$0.057 |
Electricity Demand | $73,088 | 6,209 |
kW-mo/yr
|
$11.77 |
Electricity Fees | $60,436 | - |
|
- |
Natural Gas | $184,927 | 23,060 |
MMBtu
|
$8.02 |
TOTAL YEARLY COSTS | $434,445 | |||
RECOMMENDED SAVINGS* | $179,995 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $89,150 | $489,314 |
$39,822
698,630
kWh
|
$49,328
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,822 | $728 |
$6,156
107,994
kWh
|
$3,667
-
kW-mo/yr
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $93 | $379 |
$58
1,019
kWh
|
$35
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,450 | $3,794 |
$7,802
136,878
kWh
|
$4,648
-
kW-mo/yr
|
- | |
05 | 2.4239: Eliminate or reduce compressed air usage | $1,039 | $346 |
$269
4,722
kWh
|
$769
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $198 | $144 |
$127
2,221
kWh
|
$72
-
kW-mo/yr
|
- | |
07 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $21,124 | $3,628 | - | - |
$21,124
-
MMBtu
|
|
08 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $2,349 | $3,386 |
$443
7,779
kWh
|
$1,906
-
kW-mo/yr
|
- | |
09 | 2.4133: Use most efficient type of electric motors | $3,406 | $3,393 |
$3,100
54,392
kWh
|
$306
-
kW-mo/yr
|
- | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $525 | $205 |
$332
5,824
kWh
|
$193
-
kW-mo/yr
|
- | |
11 | 2.3132: Recharge batteries on during off-peak demand periods | $2,060 | - | - |
$2,060
-
kW-mo/yr
|
- | |
12 | 2.3191: Use demand controller or load shedder | $1,025 | $1,615 |
$452
7,937
kWh
|
- |
$573
-
MMBtu
|
|
13 | 2.1224: Replace boiler | $36,754 | $57,900 | - | - |
$36,754
-
MMBtu
|
|
TOTAL RECOMMENDED | $179,995 | $564,832 |
$58,561
1,027,395
kWh
|
$62,983
-
kW-mo/yr
|
$58,451
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs