Assessment Year | 2024 |
---|---|
Principal Product | Beer |
NAICS | 312120: Breweries |
SIC | 2082: Malt Beverages |
Sales Range | $10 M to 50M |
# of Employees | 95 |
Plant Area |
51,455
ft2
|
Annual Production | 961
Tgal
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $74,604 | 977,210 |
kWh
|
$0.076 | |
Electricity Demand | $26,654 | 2,744 |
kW-mo/yr
|
$9.71 | |
Electricity Fees | $25,538 | - |
|
- | |
Natural Gas | $71,957 | 8,222 |
MMBtu
|
$8.75 | |
Waste Disposal Costs | |||||
Water Usage | $48,954 | 4,304 |
Tgal
|
$11.37 | |
TOTAL YEARLY COSTS | $247,707 | ||||
RECOMMENDED SAVINGS* | $162,347 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2531: Re-size charging openings or add movable cover or door | $2,502 | $3,692 |
$1,645
21,640
kWh
|
$627
-
kW-mo/yr
|
$231
-
MMBtu
|
- | |
02 | 2.3191: Use demand controller or load shedder | $1,368 | $3,859 |
$692
9,108
kWh
|
- |
$675
-
MMBtu
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $750 | - |
$144
1,897
kWh
|
$606
-
kW-mo/yr
|
- | - | |
04 | 2.2625: Chill water to the highest temperature possible | $475 | - |
$194
2,548
kWh
|
$281
-
kW-mo/yr
|
- | - | |
05 | 2.5113: Use direct flame impingement or infrared processing for chamber type heating | $31,214 | $13,640 | - | - |
$31,214
-
MMBtu
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $972 | $38 |
$703
9,250
kWh
|
$269
-
kW-mo/yr
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $182 | $328 |
$133
1,751
kWh
|
$49
-
kW-mo/yr
|
- | - | |
08 | 2.2414: Use waste heat from hot flue gases to preheat | $19,438 | $3,433 | - | - |
$19,438
-
MMBtu
|
- | |
09 | 2.4133: Use most efficient type of electric motors | $3,399 | $4,154 |
$2,893
38,064
kWh
|
$506
-
kW-mo/yr
|
- | - | |
10 | 2.2511: Insulate bare equipment | $2,366 | $843 | - | - |
$2,366
-
MMBtu
|
- | |
11 | 2.4239: Eliminate or reduce compressed air usage | $2,164 | - |
$2,099
27,622
kWh
|
$64
-
kW-mo/yr
|
- | - | |
12 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,947 | $546 | - | - | - | $8,947 | |
13 | 2.2113: Repair or replace steam traps | $3,324 | $1,624 | - | - |
$3,324
-
MMBtu
|
- | |
14 | 2.7311: Ventilation system to shut off when room is not in use | $774 | $36 |
$774
10,183
kWh
|
- | - | - | |
15 | 2.2511: Insulate bare equipment | $2,406 | $1,236 | - | - |
$2,406
-
MMBtu
|
- | |
16 | 2.9114: Use solar heat to make electricty | $74,328 | $441,248 |
$47,674
627,283
kWh
|
$26,654
-
kW-mo/yr
|
- | - | |
17 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,739 | $211 |
$5,655
74,411
kWh
|
$2,084
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $162,347 | $474,889 |
$62,605
823,756
kWh
|
$31,141
-
kW-mo/yr
|
$59,654
-
MMBtu
|
$8,947 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs