Assessment Year | 2024 |
---|---|
Principal Product | Metal Cans Ends |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3411: Metal Cans |
Sales Range | $10 M to 50M |
# of Employees | 178 |
Plant Area |
146,896
ft2
|
Annual Production | 17,200,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $962,938 | 21,559,824 |
kWh
|
$0.045 |
Electricity Demand | $888,009 | 33,356 |
kW-mo/yr
|
$26.62 |
Electricity Fees | $512,235 | - |
|
- |
Natural Gas | $54,932 | 6,173 |
MMBtu
|
$8.90 |
TOTAL YEARLY COSTS | $2,418,114 | |||
RECOMMENDED SAVINGS* | $66,574 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,278 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,690 | $3,413 |
$3,143
69,854
kWh
|
$2,547
-
kW-mo/yr
|
- | |
02 | 2.4239: Eliminate or reduce compressed air usage | $8,497 | $558 |
$2,885
64,130
kWh
|
$5,612
-
kW-mo/yr
|
- | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $13,248 | - | - |
$13,248
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,828 | $7,539 |
$5,981
132,914
kWh
|
$4,847
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,221 | $6,343 |
$6,198
137,736
kWh
|
$5,023
-
kW-mo/yr
|
- | |
06 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $16,247 | $16,893 |
$820
18,215
kWh
|
- |
$15,427
-
MMBtu
|
|
07 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $843 | $490 |
$843
18,739
kWh
|
- | - | |
TOTAL RECOMMENDED | $66,574 | $35,235 |
$19,870
441,589
kWh
|
$31,276
-
kW-mo/yr
|
$15,427
-
MMBtu
|
||
TOTAL IMPLEMENTED | $28,278 | $4,460 |
$6,872
152,723
kWh
|
$21,407
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs