| Assessment Year | 2023 |
|---|---|
| Principal Product | Office Space |
| NAICS | 551114: Corporate, Subsidiary, and Regional Managing Offices |
| SIC | 6541: Title Abstract Offices |
| Sales Range | less than $500 k |
| # of Employees | 80 |
| Plant Area |
33,145
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $156,215 | 2,482,398 |
kWh
|
$0.063 |
| Electricity Demand | $44,802 | 5,313 |
kW-mo/yr
|
$8.43 |
| Electricity Fees | $61,581 | - |
|
- |
| Other Energy | $1,375 | 71 |
MMBtu
|
$19.32 |
| TOTAL YEARLY COSTS | $263,972 | |||
| RECOMMENDED SAVINGS* | $61,137 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,875 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,130 | - |
$670
10,646
kWh
|
$460
-
kW-mo/yr
|
|
| 02 | 2.7135: Install occupancy sensors | $745 | $2,043 |
$436
6,936
kWh
|
$309
-
kW-mo/yr
|
|
| 03 | 2.7241: Install outside air damper / economizer on hvac unit | $4,981 | $19,147 |
$4,022
63,948
kWh
|
$959
-
kW-mo/yr
|
|
| 04 | 2.9114: Use solar heat to make electricty | $34,431 | $392,519 |
$28,952
460,280
kWh
|
$5,480
-
kW-mo/yr
|
|
| 05 | 2.7232: Replace existing hvac unit with high efficiency model | $19,851 | $34,225 |
$11,765
187,041
kWh
|
$8,086
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $61,137 | $447,933 |
$45,845
728,851
kWh
|
$15,293
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $1,875 | $2,043 |
$1,106
17,583
kWh
|
$769
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs