| Assessment Year | 2021 |
|---|---|
| Principal Product | Seals and Bearings |
| NAICS | 339991: Gasket, Packing, and Sealing Device Manufacturing |
| SIC | 3053: Gaskets, Packing, and Sealing Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 70 |
| Plant Area |
90,000
ft2
|
| Annual Production | 200,000
units
|
| Production Hrs. Annual | 3,120
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $191,567 | 3,418,078 |
kWh
|
$0.056 |
| Electricity Demand | $79,186 | 8,261 |
kW-mo/yr
|
$9.59 |
| Electricity Fees | $41,825 | - |
|
- |
| Natural Gas | $140,200 | 31,971 |
MMBtu
|
$4.39 |
| TOTAL YEARLY COSTS | $452,778 | |||
| RECOMMENDED SAVINGS* | $21,387 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,976 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,107 | $4,150 |
$1,379
24,621
kWh
|
$728
-
kW-mo/yr
|
- | |
| 02 | 2.2422: Use waste heat from hot flue gases to generate steam | $10,348 | $10,376 | - | - |
$10,348
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,708 | $10,610 |
$4,335
77,411
kWh
|
$1,373
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,063 | $5,652 |
$1,351
24,116
kWh
|
$713
-
kW-mo/yr
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $473 | - |
$230
4,103
kWh
|
$243
-
kW-mo/yr
|
- | |
| 06 | 2.2511: Insulate bare equipment | $688 | $762 |
$688
12,287
kWh
|
- | - | |
| TOTAL RECOMMENDED | $21,387 | $31,550 |
$7,983
142,538
kWh
|
$3,057
-
kW-mo/yr
|
$10,348
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $8,976 | $15,522 |
$6,632
118,422
kWh
|
$2,344
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs