Assessment Year | 2021 |
---|---|
Principal Product | Power Generation Parts |
NAICS | 336412: Aircraft Engine and Engine Parts Manufacturing |
SIC | 3646: Commercial, Industrial, and Institutional Electric Lighting Fixtures |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
200,000
ft2
|
Annual Production | 5,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $114,086 | 2,020,648 |
kWh
|
$0.056 |
Electricity Demand | $35,841 | 4,798 |
kW-mo/yr
|
$7.47 |
Electricity Fees | $25,007 | - |
|
- |
Natural Gas | $25,826 | 4,905 |
MMBtu
|
$5.27 |
TOTAL YEARLY COSTS | $200,760 | |||
RECOMMENDED SAVINGS* | $12,457 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,534 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,228 | $517 |
$1,884
33,638
kWh
|
$344
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,307 | $4,150 |
$3,641
65,023
kWh
|
$665
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $732 | $534 |
$732
13,070
kWh
|
- | - | |
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,190 | $6,120 |
$5,504
98,842
kWh
|
$2,582
-
kW-mo/yr
|
$(-2,895.8)
-
MMBtu
|
|
TOTAL RECOMMENDED | $12,457 | $11,321 |
$11,762
210,573
kWh
|
$3,591
-
kW-mo/yr
|
$(-2,895.8)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $6,534 | $4,667 |
$5,525
98,661
kWh
|
$1,009
-
kW-mo/yr
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs