Assessment Year | 2020 |
---|---|
Principal Product | Plastic Products |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 36 |
Plant Area |
47,250
ft2
|
Annual Production | 10,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $106,195 | 1,585,000 |
kWh
|
$0.067 |
Electricity Demand | $53,900 | 3,906 |
kW-mo/yr
|
$13.80 |
Electricity Fees | $7,615 | - |
|
- |
Natural Gas | $7,603 | 1,302 |
MMBtu
|
$5.84 |
TOTAL YEARLY COSTS | $175,313 | |||
RECOMMENDED SAVINGS* | $8,935 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $329 | $167 |
$216
3,229
kWh
|
$112
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,040 | $167 |
$2,040
30,313
kWh
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,788 | $861 |
$2,000
29,713
kWh
|
$789
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,778 | $2,589 |
$2,710
40,260
kWh
|
$1,068
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $8,935 | $3,784 |
$6,966
103,516
kWh
|
$1,969
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs