ITAC Assessment: IC0188
ITAC logo
ITAC Assessment: IC0188
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2011
Principal Product batteries
NAICS 335911: Storage Battery Manufacturing
SIC 3691: Storage Batteries
Sales Range $1
M
to 5
M
# of Employees 287
Plant Area 275,000
ft2
Annual Production 1,700
pieces
Production Hrs. Annual 1,992
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $519,271 17,633,250
kWh
Electricity Demand $53,649 2,737
kW-mo/yr
Electricity Fees $17,138 -
Natural Gas $575,767 100,723
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $40,824 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Ancillary Material Cost Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $20,742 $44,268 $7,551
260,431
kWh
$13,216
-
kW-mo/yr
$(-619.0) $594
02 2.7135: Install occupancy sensors $244 $541 $48
1,657
kWh
$196
-
kW-mo/yr
- -
03 2.6218: Turn off equipment when not in use $9,096 - $9,096
324,864
kWh
- - -
04 2.6211: Conserve energy by efficient use of vending machines $285 - $148
5,100
kWh
$137
-
kW-mo/yr
- -
05 2.6218: Turn off equipment when not in use $422 - $83
2,871
kWh
$339
-
kW-mo/yr
- -
06 2.2135: Repair and eliminate steam leaks $3,582 $690 $3,582
123,510
kWh
- - -
07 2.3132: Recharge batteries on during off-peak demand periods $6,453 - - $6,453
-
kW-mo/yr
- -
TOTAL RECOMMENDED $40,824 $45,499 $20,508
718,433
kWh
$20,341
-
kW-mo/yr
$(-619.0) $594
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs