Assessment Year | 2010 |
---|---|
Principal Product | Automotive Acoustical Products |
NAICS | 326299: All Other Rubber Product Manufacturing |
SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 131 |
Plant Area |
145,000
ft2
|
Annual Production | 6,800,000
pieces
|
Production Hrs. Annual | 4,179
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $177,974 | 2,968,960 |
kWh
|
$0.060 |
Electricity Demand | $123,886 | 8,621 |
kW-mo/yr
|
$14.37 |
Natural Gas | $37,599 | 4,895 |
MMBtu
|
$7.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,042 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,092 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,901 | $6,914 |
$2,066
34,375
kWh
|
$1,594
-
kW-mo/yr
|
- | $125 | $116 | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $91 | $58 |
$10
165
kWh
|
$72
-
kW-mo/yr
|
- | $8 | - | $1 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,223 | $99,311 |
$15,889
264,802
kWh
|
$10,936
-
kW-mo/yr
|
- | $1,331 | - | $(-1,933.0) | |
04 | 2.7135: Install occupancy sensors | $517 | $1,317 |
$267
4,578
kWh
|
$250
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,545 | $345 |
$4,545
75,756
kWh
|
- | - | - | - | - | |
06 | 2.4133: Use most efficient type of electric motors | $1,860 | $5,879 |
$1,102
18,346
kWh
|
$758
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $2,143 | $1,178 | - | - |
$2,143
-
MMBtu
|
- | - | - | |
08 | 2.2223: Enhance sensitivity of temperature control and cutoff | $438 | $1 | - | - |
$438
-
MMBtu
|
- | - | - | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $324 | $1 |
$324
5,400
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $40,042 | $115,004 |
$24,203
403,422
kWh
|
$13,610
-
kW-mo/yr
|
$2,581
-
MMBtu
|
$1,464 | $116 | $(-1,932.0) | ||
TOTAL IMPLEMENTED | $31,092 | $99,657 |
$20,758
345,958
kWh
|
$10,936
-
kW-mo/yr
|
- | $1,331 | - | $(-1,933.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs