Assessment Year | 2008 |
---|---|
Principal Product | Raw Materials |
NAICS | 332991: Ball and Roller Bearing Manufacturing |
SIC | 3562: Ball and Roller Bearings |
Sales Range | $1 M to 5M |
# of Employees | 130 |
Plant Area |
242,088
ft2
|
Annual Production | 245,000
pieces
|
Production Hrs. Annual | 3,428
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $145,071 | 2,293,080 |
kWh
|
$0.063 |
Electricity Demand | $53,389 | 5,010 |
kW-mo/yr
|
$10.66 |
Natural Gas | $101,871 | 13,596 |
MMBtu
|
$7.49 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,662 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $57,047 | $112,631 |
$38,445
610,231
kWh
|
$20,329
-
kW-mo/yr
|
- | $(-1,658.0) | $(-69.0) | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $556 | $4,664 |
$311
4,913
kWh
|
$182
-
kW-mo/yr
|
- | - | $63 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,604 | $14,300 |
$3,106
49,291
kWh
|
$2,147
-
kW-mo/yr
|
- | $129 | $(-778.0) | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,134 | $391 |
$569
9,024
kWh
|
$416
-
kW-mo/yr
|
- | $172 | $(-23.0) | |
05 | 2.7135: Install occupancy sensors | $7,958 | $14,655 |
$4,813
76,396
kWh
|
$3,145
-
kW-mo/yr
|
- | - | - | |
06 | 2.4133: Use most efficient type of electric motors | $466 | $3,785 |
$242
3,842
kWh
|
$224
-
kW-mo/yr
|
- | - | - | |
07 | 4.811: Demolish old building to reduce tax and insurance bills | $2,172 | $4,500 | - | - |
$2,172
-
MMBtu
|
- | - | |
08 | 4.512: Condense operation into one building | $3,114 | - |
$508
8,072
kWh
|
$416
-
kW-mo/yr
|
$2,082
-
MMBtu
|
$108 | - | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $611 | - |
$227
3,600
kWh
|
$384
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $77,662 | $154,926 |
$48,221
765,369
kWh
|
$27,243
-
kW-mo/yr
|
$4,254
-
MMBtu
|
$(-1,249.0) | $(-807.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs