ITAC Assessment: IC0145
ITAC logo
ITAC Assessment: IC0145
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2008
Principal Product Raw Materials
NAICS 332991: Ball and Roller Bearing Manufacturing
SIC 3562: Ball and Roller Bearings
Sales Range $1
M
to 5
M
# of Employees 130
Plant Area 242,088
ft2
Annual Production 245,000
pieces
Production Hrs. Annual 3,428
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $145,071 2,293,080
kWh
Electricity Demand $53,389 5,010
kW-mo/yr
Natural Gas $101,871 13,596
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $77,662 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $57,047 $112,631 $38,445
610,231
kWh
$20,329
-
kW-mo/yr
- $(-1,658.0) $(-69.0)
02 2.7142: Utilize higher efficiency lamps and/or ballasts $556 $4,664 $311
4,913
kWh
$182
-
kW-mo/yr
- - $63
03 2.7142: Utilize higher efficiency lamps and/or ballasts $4,604 $14,300 $3,106
49,291
kWh
$2,147
-
kW-mo/yr
- $129 $(-778.0)
04 2.7142: Utilize higher efficiency lamps and/or ballasts $1,134 $391 $569
9,024
kWh
$416
-
kW-mo/yr
- $172 $(-23.0)
05 2.7135: Install occupancy sensors $7,958 $14,655 $4,813
76,396
kWh
$3,145
-
kW-mo/yr
- - -
06 2.4133: Use most efficient type of electric motors $466 $3,785 $242
3,842
kWh
$224
-
kW-mo/yr
- - -
07 4.811: Demolish old building to reduce tax and insurance bills $2,172 $4,500 - - $2,172
-
MMBtu
- -
08 4.512: Condense operation into one building $3,114 - $508
8,072
kWh
$416
-
kW-mo/yr
$2,082
-
MMBtu
$108 -
09 2.6211: Conserve energy by efficient use of vending machines $611 - $227
3,600
kWh
$384
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $77,662 $154,926 $48,221
765,369
kWh
$27,243
-
kW-mo/yr
$4,254
-
MMBtu
$(-1,249.0) $(-807.0)
TOTAL IMPLEMENTED - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs