Assessment Year | 2008 |
---|---|
Principal Product | Plastic appliance parts |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 80 |
Plant Area |
18,000
ft2
|
Annual Production | 61,000,000
pieces
|
Production Hrs. Annual | 5,976
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $110,742 | 2,253,600 |
kWh
|
$0.049 |
Electricity Demand | $61,232 | 5,030 |
kW-mo/yr
|
$12.17 |
Electricity Fees | $4,568 | - |
|
- |
Natural Gas | $3,299 | 282 |
MMBtu
|
$11.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,628 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $14,222 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,363 | $12,122 |
$2,886
58,888
kWh
|
$1,436
-
kW-mo/yr
|
- | $41 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,224 | $5,101 |
$1,203
24,571
kWh
|
$754
-
kW-mo/yr
|
- | $267 | |
03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $461 | - |
$193
3,931
kWh
|
$268
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $533 | $781 |
$227
4,650
kWh
|
$306
-
kW-mo/yr
|
- | - | |
05 | 2.7124: Make a practice of turning off lights when not needed | $68 | - |
$44
880
kWh
|
$24
-
kW-mo/yr
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $1,031 | $4,364 |
$690
14,088
kWh
|
$341
-
kW-mo/yr
|
- | - | |
07 | 2.4239: Eliminate or reduce compressed air usage | $9,002 | $2,000 |
$5,728
116,891
kWh
|
$3,274
-
kW-mo/yr
|
- | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $431 | - |
$431
8,805
kWh
|
- | - | - | |
09 | 2.7224: Reduce space conditioning during non-working hours | $222 | - | - | - |
$222
-
MMBtu
|
- | |
10 | 2.9112: Use solar heat to heat water | $305 | $1,965 |
$122
2,486
kWh
|
$183
-
kW-mo/yr
|
- | - | |
11 | 2.6211: Conserve energy by efficient use of vending machines | $307 | - |
$88
1,800
kWh
|
$219
-
kW-mo/yr
|
- | - | |
12 | 2.6231: Utilize controls to operate equipment only when needed | $48 | - |
$24
488
kWh
|
$24
-
kW-mo/yr
|
- | - | |
13 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $633 | $920 |
$633
12,928
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $19,628 | $27,253 |
$12,269
250,406
kWh
|
$6,829
-
kW-mo/yr
|
$222
-
MMBtu
|
$308 | ||
TOTAL IMPLEMENTED | $14,222 | $13,166 |
$8,742
178,427
kWh
|
$4,991
-
kW-mo/yr
|
$222
-
MMBtu
|
$267 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs