Assessment Year | 2008 |
---|---|
Principal Product | Pharmaceutical Products |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
180,000
ft2
|
Annual Production | 100,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $956,802 | 12,535,072 |
kWh
|
$0.076 |
Other Energy | $1,504,839 | 130,784 |
MMBtu
|
$11.51 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $322,473 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $74,077 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Other Energy Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $30,325 | $6,000 |
$30,325
397,440
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,733 | $24,016 |
$21,733
284,832
kWh
|
- | - | |
03 | 2.7135: Install occupancy sensors | $23,283 | $37,500 |
$23,283
305,148
kWh
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,400 | - |
$1,400
36,603
kWh
|
- | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $23,800 | $49,250 |
$23,800
1,252,000
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $2,794 | $14,000 |
$2,794
36,603
kWh
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,000 | $11,500 | - | $10,000 | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $15,750 | $1,400 | - | $15,750 | - | |
09 | 2.2136: Install / repair insulation on steam lines | $59,840 | $25,152 | - | - |
$59,840
-
MMBtu
|
|
10 | 2.2113: Repair or replace steam traps | $19,800 | $17,250 | - | - |
$19,800
-
MMBtu
|
|
11 | 2.7425: Clean or color roof to reduce solar load | $113,748 | $180,000 |
$113,748
1,490,100
kWh
|
- | - | |
TOTAL RECOMMENDED | $322,473 | $366,068 |
$217,083
3,802,726
kWh
|
$25,750 |
$79,640
-
MMBtu
|
||
TOTAL IMPLEMENTED | $74,077 | $100,166 |
$48,327
1,573,435
kWh
|
$25,750 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Other Energy Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs