Assessment Year | 2006 |
---|---|
Principal Product | transformer manufacturer |
NAICS | 335313: Switchgear and Switchboard Apparatus Manufacturing |
SIC | 3613: Switchgear and Switchboard Apparatus |
Sales Range | $100 M to 500M |
# of Employees | 1,800 |
Plant Area |
1,092,131
ft2
|
Annual Production | 50,000,000
pieces
|
Production Hrs. Annual | 8,520
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,637,019 | 47,377,583 |
kWh
|
$0.056 |
Electricity Demand | $410,502 | 91,918 |
kW-mo/yr
|
$4.47 |
Electricity Fees | $87,894 | - |
|
- |
Natural Gas | $1,718,285 | 202,065 |
MMBtu
|
$8.50 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $293,187 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $66,838 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 3.5145: Recover and reuse spent acid baths | $32,160 | $82,800 | - | - | - |
$32,160
-
gal
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,829 | $600 |
$1,829
32,647
kWh
|
- | - | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $34,559 | $114,725 |
$27,025
482,581
kWh
|
$5,775
-
kW-mo/yr
|
- | - | $270 | $1,489 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,402 | $61,775 |
$14,819
264,617
kWh
|
$2,852
-
kW-mo/yr
|
- | - | $(-43.0) | $7,774 | |
05 | 2.2437: Recover waste heat from equipment | $33,836 | $144,000 |
$(-1,664.0)
(-29,721)
kWh
|
$(-183.0)
-
kW-mo/yr
|
$35,683
-
MMBtu
|
- | - | - | |
06 | 2.8114: Change rate schedules or other changes in utility service | $130,000 | - |
$130,000
-
kWh
|
- | - | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,048 | $38,744 |
$2,867
51,202
kWh
|
$313
-
kW-mo/yr
|
- | - | $776 | $1,092 | |
08 | 2.7232: Replace existing hvac unit with high efficiency model | $30,353 | $312,000 |
$(-6,535.0)
(-116,695)
kWh
|
$(-840.0)
-
kW-mo/yr
|
$37,728
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $293,187 | $754,644 |
$168,341
684,631
kWh
|
$7,917
-
kW-mo/yr
|
$73,411
-
MMBtu
|
$32,160
-
gal
|
$1,003 | $10,355 | ||
TOTAL IMPLEMENTED | $66,838 | $215,844 |
$46,540
831,047
kWh
|
$8,940
-
kW-mo/yr
|
- | - | $1,003 | $10,355 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs