ITAC Assessment: IC0069
ITAC logo
ITAC Assessment: IC0069
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2003
Principal Product Resin, Colorant and Refinished Paint
NAICS 325510: Paint and Coating Manufacturing
SIC 2851: Paints, Varnishes, Lacquers, Enamels, and Allied Products
Sales Range $10
M
to 50
M
# of Employees 140
Plant Area 302,000
ft2
Annual Production 6,000
Tgal
Production Hrs. Annual 6,120
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $179,330 5,927,925
kWh
Electricity Demand $46,076 12,834
kW-mo/yr
Electricity Fees $187,098 -
Natural Gas $185,728 39,343
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $72,801 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $36,358

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $12,411 $2,200 $11,125
182,396
kWh
$1,286
-
kW-mo/yr
- -
02 2.2136: Install / repair insulation on steam lines $4,983 $8,812 - - $4,983
-
MMBtu
-
03 2.1233: Analyze flue gas for proper air/fuel ratio $1,894 $5,280 - - $1,894
-
MMBtu
-
04 2.1113: Reduce combustion air flow to optimum $10,894 $10,560 - - $10,894
-
MMBtu
-
05 2.2113: Repair or replace steam traps $6,176 $341 - - $6,176
-
MMBtu
-
06 2.5194: Redesign process $579 $1,984 $519
8,491
kWh
$60
-
kW-mo/yr
- -
07 2.7243: Improve air circulation with destratification fans / other methods $4,246 $26,552 $(-832.0)
(-13,637)
kWh
$(-192.0)
-
kW-mo/yr
$5,675
-
MMBtu
$(-405.0)
08 2.7491: Insulate glazing, walls, ceilings, and roofs $31,618 $251,040 - - $31,618
-
MMBtu
-
TOTAL RECOMMENDED $72,801 $306,769 $10,812
177,250
kWh
$1,154
-
kW-mo/yr
$61,240
-
MMBtu
$(-405.0)
TOTAL IMPLEMENTED $36,358 $27,193 $11,125
182,396
kWh
$1,286
-
kW-mo/yr
$23,947
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs