Assessment Year | 2014 |
---|---|
Principal Product | Plastic Bins |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 145 |
Plant Area |
80,000
ft2
|
Annual Production | 50,000,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $519,883 | 14,572,992 |
kWh
|
$0.036 |
Electricity Demand | $396,095 | 24,578 |
kW-mo/yr
|
$16.12 |
Electricity Fees | $31,198 | - |
|
- |
Natural Gas | $10,737 | 1,858 |
MMBtu
|
$5.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,058 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,843 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $9,002 | $11,806 |
$5,559
155,721
kWh
|
$3,443
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $10,226 | $100 | - |
$8,499
-
kW-mo/yr
|
$1,727 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,843 | $365 |
$4,227
118,374
kWh
|
$2,616
-
kW-mo/yr
|
- | |
04 | 2.7134: Use photocell controls | $1,490 | $810 |
$621
17,384
kWh
|
$869
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,000 | $2,939 |
$618
17,297
kWh
|
$382
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $577 | $1,116 |
$577
16,160
kWh
|
- | - | |
07 | 2.7144: Install spectral reflectors / delamp | $646 | $210 |
$399
11,182
kWh
|
$247
-
kW-mo/yr
|
- | |
08 | 2.6218: Turn off equipment when not in use | $274 | $75 |
$274
7,687
kWh
|
- | - | |
TOTAL RECOMMENDED | $30,058 | $17,421 |
$12,275
343,805
kWh
|
$16,056
-
kW-mo/yr
|
$1,727 | ||
TOTAL IMPLEMENTED | $6,843 | $365 |
$4,227
118,374
kWh
|
$2,616
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs