Assessment Year | 2013 |
---|---|
Principal Product | metal buildings |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3449: Miscellaneous Structural Metal Work |
Sales Range | $50 M to 100M |
# of Employees | 174 |
Plant Area |
265,000
ft2
|
Annual Production | 33,000
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $285,400 | 3,762,445 |
kWh
|
$0.076 |
Electricity Demand | $98,556 | 12,353 |
kW-mo/yr
|
$7.98 |
Electricity Fees | $18,861 | - |
|
- |
Natural Gas | $64,789 | 9,011 |
MMBtu
|
$7.19 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $54,564 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,952 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,004 | $710 |
$1,667
21,965
kWh
|
$337
-
kW-mo/yr
|
- | |
02 | 2.4239: Eliminate or reduce compressed air usage | $1,170 | $105 |
$1,170
15,480
kWh
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,050 | $2,500 |
$1,705
22,464
kWh
|
$345
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $413 | $1,388 |
$413
5,435
kWh
|
- | - | |
05 | 2.6218: Turn off equipment when not in use | $19,132 | $8,000 |
$15,913
209,664
kWh
|
$3,219
-
kW-mo/yr
|
- | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $4,973 | $1,700 |
$4,973
65,520
kWh
|
- | - | |
07 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $8,980 | $22,500 |
$6,394
84,240
kWh
|
$2,586
-
kW-mo/yr
|
- | |
08 | 2.6218: Turn off equipment when not in use | $2,461 | $210 | - | - |
$2,461
-
MMBtu
|
|
09 | 2.7492: Use proper thickness of insulation on building envelope | $280 | $110 | - | - |
$280
-
MMBtu
|
|
10 | 2.4133: Use most efficient type of electric motors | $4,264 | $15,781 |
$3,547
46,739
kWh
|
$717
-
kW-mo/yr
|
- | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,837 | $16,072 |
$7,295
96,111
kWh
|
$1,542
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $54,564 | $69,076 |
$43,077
567,618
kWh
|
$8,746
-
kW-mo/yr
|
$2,741
-
MMBtu
|
||
TOTAL IMPLEMENTED | $22,952 | $35,861 |
$17,895
235,770
kWh
|
$2,596
-
kW-mo/yr
|
$2,461
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs