Assessment Year | 2013 |
---|---|
Principal Product | Hydraulic pumps and motors |
NAICS | 333611: Turbine and Turbine Generator Set Units Manufacturing |
SIC | 3511: Steam, Gas, and Hydraulic Turbines, and Turbine Generator Set Units |
Sales Range | $100 M to 500M |
# of Employees | 491 |
Plant Area |
359,060
ft2
|
Annual Production | 500,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,695,113 | 24,854,540 |
kWh
|
$0.068 |
Electricity Demand | $148,946 | 50,677 |
kW-mo/yr
|
$2.94 |
Natural Gas | $130,769 | 30,334 |
MMBtu
|
$4.31 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $139,054 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $128,741 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $112,998 | $128,338 |
$106,545
1,564,536
kWh
|
$6,453
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $2,326 | $2,120 |
$2,326
34,157
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,452 | $2,000 |
$10,798
158,556
kWh
|
$654
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,291 | $105 |
$4,045
59,405
kWh
|
$246
-
kW-mo/yr
|
- | |
05 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $7,659 | $3,000 |
$7,269
106,733
kWh
|
$390
-
kW-mo/yr
|
- | |
06 | 2.1213: Direct warmest air to combustion intake | $328 | $200 | - | - |
$328
-
MMBtu
|
|
TOTAL RECOMMENDED | $139,054 | $135,763 |
$130,983
1,923,387
kWh
|
$7,743
-
kW-mo/yr
|
$328
-
MMBtu
|
||
TOTAL IMPLEMENTED | $128,741 | $130,443 |
$121,388
1,782,497
kWh
|
$7,353
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs