ITAC Assessment: IA0438
ITAC logo
ITAC Assessment: IA0438
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2009
Principal Product Newspapers and Newspaper Inserts
NAICS 511110: Newspaper Publishers
SIC 2711: Newspapers: Publishing, or Publishing and Printing
Sales Range $10
M
to 50
M
# of Employees 162
Plant Area 370,000
ft2
Annual Production 71,000,000
pieces
Production Hrs. Annual 7,280
hrs
Location (State) Nebraska

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $215,555 7,984,267
kWh
Electricity Demand $18,637 2,356
kW-mo/yr
Other Energy $698,114 27,548
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $54,037 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $37,892

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $18,772 $59,001 $12,789
466,780
kWh
$5,983
-
kW-mo/yr
-
02 2.7124: Make a practice of turning off lights when not needed $259 $50 $185
6,755
kWh
$74
-
kW-mo/yr
-
03 2.7122: Disconnect ballasts $330 $250 $224
8,154
kWh
$106
-
kW-mo/yr
-
04 2.7135: Install occupancy sensors $799 $462 $799
29,171
kWh
- -
05 2.7111: Reduce illumination to minimum necessary levels $346 $515 $346
12,613
kWh
- -
06 2.7131: Add area lighting switches $7,861 $2,200 $7,861
217,584
kWh
- -
07 3.7196: Use re-usable filters $15,000 $7,540 - - $15,000
-
lb
08 2.7224: Reduce space conditioning during non-working hours $10,670 $2,000 $10,670
389,647
kWh
- -
TOTAL RECOMMENDED $54,037 $72,018 $32,874
1,130,704
kWh
$6,163
-
kW-mo/yr
$15,000
-
lb
TOTAL IMPLEMENTED $37,892 $63,501 $31,729
1,088,920
kWh
$6,163
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs