| Assessment Year | 2007 |
|---|---|
| Principal Product | Aviation Electronics |
| NAICS | 334511: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical System and Instrument Manufactur |
| SIC | 3812: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical Systems and Instruments |
| Sales Range | $10 M to 50M |
| # of Employees | 268 |
| Plant Area |
46,000
ft2
|
| Annual Production | 12,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Iowa |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $88,345 | 2,041,000 |
kWh
|
$0.043 |
| Electricity Demand | $18,473 | 489 |
kW-mo/yr
|
$37.78 |
| Natural Gas | $3,111 | 339 |
MMBtu
|
$9.18 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $13,356 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $9,366 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,366 | $16,698 |
$8,235
192,815
kWh
|
$1,131
-
kW-mo/yr
|
|
| 02 | 2.7135: Install occupancy sensors | $3,284 | $1,309 |
$3,284
76,902
kWh
|
- | |
| 03 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $215 | $25 |
$187
4,374
kWh
|
$28
-
kW-mo/yr
|
|
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $491 | $700 |
$430
10,071
kWh
|
$61
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $13,356 | $18,732 |
$12,136
284,162
kWh
|
$1,220
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $9,366 | $16,698 |
$8,235
192,815
kWh
|
$1,131
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs