Assessment Year 2006
Principal Product wood furniture
NAICS 337215: Showcase, Partition, Shelving, and Locker Manufacturing
SIC 2511: Wood Household Furniture, Except Upholstered
Sales Range $10
M
to 50
M
# of Employees 132
Plant Area 120,000
ft2
Annual Production 112,500
pieces
Production Hrs. Annual 2,550
hrs
Location (State) Iowa

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $86,563 2,554,276
kWh
Electricity Demand $137,722 12,804
kW-mo/yr
Electricity Fees $3,590 -
Natural Gas $67,592 5,567
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $24,676 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $24,098

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $8,020 $541 $3,217
94,816
kWh
$4,803
-
kW-mo/yr
02 2.4133: Use most efficient type of electric motors $578 $5,251 $220
6,484
kWh
$358
-
kW-mo/yr
03 2.6212: Turn off equipment during breaks, reduce operating time $762 - $762
22,490
kWh
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $1,978 - $791
23,340
kWh
$1,187
-
kW-mo/yr
05 2.7142: Utilize higher efficiency lamps and/or ballasts $5,479 $16,536 $2,218
65,437
kWh
$3,261
-
kW-mo/yr
06 2.7131: Add area lighting switches $1,508 $1,200 $903
17,850
kWh
$605
-
kW-mo/yr
07 2.7135: Install occupancy sensors $636 $1,155 $636
18,775
kWh
-
08 4.454: Modify startup/shutdown times $5,715 - $5,715
168,582
kWh
-
TOTAL RECOMMENDED $24,676 $24,683 $14,462
417,774
kWh
$10,214
-
kW-mo/yr
TOTAL IMPLEMENTED $24,098 $19,432 $14,242
411,290
kWh
$9,856
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs