| Assessment Year | 1999 |
|---|---|
| Principal Product | horse and livestock trailers |
| NAICS |
n/a
|
| SIC | 3799: Transportation Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 90 |
| Plant Area |
100,000
ft2
|
| Annual Production | 2,200
pieces
|
| Production Hrs. Annual | 2,250
hrs
|
| Location (State) | Iowa |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $27,689 | 735,932 |
kWh
|
$0.038 |
| Electricity Demand | $20,214 | 3,408 |
kW-mo/yr
|
$5.93 |
| Natural Gas | $47,708 | 11,761 |
MMBtu
|
$4.06 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,033 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,900 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,917 | $5,903 |
$1,042
27,843
kWh
|
$875
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,526 | - |
$829
21,981
kWh
|
$697
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.7135: Install occupancy sensors | $387 | $798 |
$387
10,258
kWh
|
- | - | - | - | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,152 | $257 |
$625
16,706
kWh
|
$527
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 2.2437: Recover waste heat from equipment | $847 | $1,105 | - | - |
$847
-
MMBtu
|
- | - | - | |
| 06 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $900 | $100 | - | - | - |
$900
-
lb
|
- | - | |
| 07 | 3.5218: Reuse / recycle/ sell rubber products | $625 | $50 | - | - | - |
$625
-
lb
|
- | - | |
| 08 | 3.6192: Use a less expensive method of waste removal | $253 | $50 | - | - | - | - | - | $253 | |
| 09 | 3.8142: Distill contaminated solvents for reuse | $16,258 | $7,853 | - | - | - | - | - | $16,258 | |
| 10 | 4.131: Modify process to reduce material use/cost | $3,710 | $6,923 | - | - | - | - | - | $3,710 | |
| 11 | 4.131: Modify process to reduce material use/cost | $1,458 | $50 | - | - | - | - | $2,219 | $(-761.0) | |
| TOTAL RECOMMENDED | $29,033 | $23,089 |
$2,883
76,788
kWh
|
$2,099
-
kW-mo/yr
|
$847
-
MMBtu
|
$1,525
-
lb
|
$2,219 | $19,460 | ||
| TOTAL IMPLEMENTED | $6,900 | $7,315 |
$2,496
66,530
kWh
|
$2,099
-
kW-mo/yr
|
$847
-
MMBtu
|
- | $2,219 | $(-761.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs