Assessment Year | 1996 |
---|---|
Principal Product | Edible Stocks and Broths |
NAICS |
n/a
|
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
64,000
ft2
|
Annual Production | 45,000,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $144,740 | 4,458,968 |
kWh
|
$0.032 |
Electricity Demand | $32,297 | 10,272 |
kW-mo/yr
|
$3.14 |
Electricity Fees | $785 | - |
|
- |
Natural Gas | $335,200 | 172,147 |
MMBtu
|
$1.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,369 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,964 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,888 | $1,000 | - | - |
$6,888
-
MMBtu
|
- | - | |
02 | 2.1213: Direct warmest air to combustion intake | $850 | $165 | - | - |
$850
-
MMBtu
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $405 | $1,186 |
$320
15,533
kWh
|
$85
-
kW-mo/yr
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $350 | $229 |
$271
13,189
kWh
|
$79
-
kW-mo/yr
|
- | - | - | |
05 | 4.652: Replace existing equipment with more suitable substitutes | $356 | - | - | - | - | - | $356 | |
06 | 3.4111: Use closed cycle process to minimize waste water production | $2,520 | $2,500 | - | - | - |
$2,520
-
Tgal
|
- | |
TOTAL RECOMMENDED | $11,369 | $5,080 |
$591
28,722
kWh
|
$164
-
kW-mo/yr
|
$7,738
-
MMBtu
|
$2,520
-
Tgal
|
$356 | ||
TOTAL IMPLEMENTED | $10,964 | $3,894 |
$271
13,189
kWh
|
$79
-
kW-mo/yr
|
$7,738
-
MMBtu
|
$2,520
-
Tgal
|
$356 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs