| Assessment Year | 1995 |
|---|---|
| Principal Product | aluminum cans and ends |
| NAICS |
n/a
|
| SIC | 3411: Metal Cans |
| Sales Range | $5 M to 10M |
| # of Employees | 96 |
| Plant Area |
105,000
ft2
|
| Annual Production | 50,000,000
lb
|
| Production Hrs. Annual | 8,520
hrs
|
| Location (State) | Iowa |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $313,032 | 6,840,563 |
kWh
|
$0.046 |
| Natural Gas | $11,690 | 2,759 |
MMBtu
|
$4.24 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $32,897 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,689 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,304 | $79,400 |
$11,304
247,069
kWh
|
|
| 02 | 2.4133: Use most efficient type of electric motors | $12,241 | $1,577 |
$12,241
267,585
kWh
|
|
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,217 | $1,816 |
$4,217
92,321
kWh
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,911 | $520 |
$1,911
41,911
kWh
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,877 | $8,050 |
$2,877
63,013
kWh
|
|
| 06 | 2.7135: Install occupancy sensors | $203 | $539 |
$203
4,396
kWh
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $144 | $270 |
$144
3,224
kWh
|
|
| TOTAL RECOMMENDED | $32,897 | $92,172 |
$32,897
719,519
kWh
|
||
| TOTAL IMPLEMENTED | $23,689 | $81,247 |
$23,689
517,878
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs