| Assessment Year | 2000 |
|---|---|
| Principal Product | Plastic Bags |
| NAICS |
n/a
|
| SIC | 3081: Unsupported Plastics Film and Sheet |
| Sales Range | $5 M to 10M |
| # of Employees | 40 |
| Plant Area |
30,000
ft2
|
| Annual Production | 13,000,000
lb
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $245,929 | 3,115,768 |
kWh
|
$0.079 |
| Electricity Demand | $53,568 | 5,236 |
kW-mo/yr
|
$10.23 |
| Electricity Fees | $(-26,525.0) | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $86,226 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,121 | $6,030 | n/a |
$5,197
65,944
kWh
|
$924
-
kW-mo/yr
|
- | - | - |
| 02 | 2.7135: Install occupancy sensors | $725 | $200 | n/a |
$725
9,086
kWh
|
- | - | - | - |
| 03 | 2.4133: Use most efficient type of electric motors | $5,922 | $15,200 | n/a |
$5,922
75,029
kWh
|
- | - | - | - |
| 04 | 2.2511: Insulate bare equipment | $8,538 | $1,008 | n/a |
$8,538
108,148
kWh
|
- | - | - | - |
| 05 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $60,015 | $400,000 | n/a | - |
$276,861
-
kW-mo/yr
|
$(-216,846.0)
-
MMBtu
|
- | - |
| 06 | 4.424: Improve space comfort conditioning | $4,365 | $500 | n/a | - | - | - | - | $4,365 |
| 07 | 3.5313: Increase amount of waste recovered for resale | $540 | $100 | n/a | - | - | - |
$540
-
lb
|
- |
| TOTAL RECOMMENDED | $86,226 | $423,038 |
$20,382
258,207
kWh
|
$277,785
-
kW-mo/yr
|
$(-216,846.0)
-
MMBtu
|
$540
-
lb
|
$4,365 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs