Assessment Year | 2000 |
---|---|
Principal Product | Precious Metal Recovery |
NAICS |
n/a
|
SIC | 3341: Secondary Smelting and Refining of Nonferrous Metals |
Sales Range | $10 M to 50M |
# of Employees | 230 |
Plant Area |
210,000
ft2
|
Annual Production | 1,800,000
lb
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $907,054 | 13,300,997 |
kWh
|
$0.068 |
Electricity Demand | $229,022 | 23,294 |
kW-mo/yr
|
$9.83 |
Electricity Fees | $(-107,960.0) | - |
|
- |
Natural Gas | $932,196 | 212,362 |
MMBtu
|
$4.39 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $104,379 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,858 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,337 | $24,765 |
$7,554
110,785
kWh
|
$2,783
-
kW-mo/yr
|
- | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $1,354 | $3,000 |
$1,126
16,413
kWh
|
$228
-
kW-mo/yr
|
- | - | |
03 | 2.7124: Make a practice of turning off lights when not needed | $4,650 | $548 |
$4,650
68,288
kWh
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $11,898 | $5,000 |
$11,898
174,385
kWh
|
- | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $9,645 | $10,005 |
$9,645
141,266
kWh
|
- | - | - | |
06 | 2.6218: Turn off equipment when not in use | $4,569 | - |
$4,569
67,116
kWh
|
- | - | - | |
07 | 2.2511: Insulate bare equipment | $49,535 | $11,088 |
$49,535
726,260
kWh
|
- | - | - | |
08 | 2.2414: Use waste heat from hot flue gases to preheat | $10,726 | $4,167 | - | - |
$10,726
-
MMBtu
|
- | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $1,665 | $222 | - | - | - | $1,665 | |
TOTAL RECOMMENDED | $104,379 | $58,795 |
$88,977
1,304,513
kWh
|
$3,011
-
kW-mo/yr
|
$10,726
-
MMBtu
|
$1,665 | ||
TOTAL IMPLEMENTED | $27,858 | $15,775 |
$26,193
383,939
kWh
|
- | - | $1,665 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs