Assessment Year | 1999 |
---|---|
Principal Product | Gyroscopes |
NAICS |
n/a
|
SIC | 3812: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical Systems and Instruments |
Sales Range | $50 M to 100M |
# of Employees | 420 |
Plant Area |
132,000
ft2
|
Annual Production | 39,000
lb
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $880,647 | 15,550,997 |
kWh
|
$0.057 |
Electricity Demand | $289,416 | 28,192 |
kW-mo/yr
|
$10.27 |
Electricity Fees | $(-209,346.0) | - |
|
- |
Natural Gas | $301,600 | 57,834 |
MMBtu
|
$5.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $52,694 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,058 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $28,880 | $600 |
$20,960
370,457
kWh
|
$7,920
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $11,756 | $15,000 |
$11,756
207,796
kWh
|
- | - | |
03 | 2.7135: Install occupancy sensors | $5,242 | $10,000 |
$5,242
92,614
kWh
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $2,590 | - |
$2,590
45,721
kWh
|
- | - | |
05 | 2.7124: Make a practice of turning off lights when not needed | $590 | - |
$590
10,551
kWh
|
- | - | |
06 | 2.6218: Turn off equipment when not in use | $1,738 | - |
$1,738
30,774
kWh
|
- | - | |
07 | 2.2136: Install / repair insulation on steam lines | $1,898 | $2,625 | - | - |
$1,898
-
MMBtu
|
|
TOTAL RECOMMENDED | $52,694 | $28,225 |
$42,876
757,913
kWh
|
$7,920
-
kW-mo/yr
|
$1,898
-
MMBtu
|
||
TOTAL IMPLEMENTED | $49,058 | $25,600 |
$41,138
727,139
kWh
|
$7,920
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs