Assessment Year | 1994 |
---|---|
Principal Product | Metallic Powders |
NAICS |
n/a
|
SIC | 3399: Primary Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 87 |
Plant Area |
109,000
ft2
|
Annual Production | 8,200,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $543,958 | 6,256,741 |
kWh
|
$0.087 |
Fuel Oil #4 | $75,550 | 15,921 |
MMBtu
|
$4.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $277,484 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,941 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #2 Savings | Fuel Oil #4 Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,503 | $1,976 |
$2,503
28,722
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,842 | $4,383 |
$1,842
21,102
kWh
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $2,282 | $2,977 |
$2,282
26,377
kWh
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $7,314 | $1,500 |
$7,314
84,115
kWh
|
- | - | |
05 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $263,543 | $1,260,000 |
$440,040
5,061,548
kWh
|
$(-221,706.0)
-
MMBtu
|
$45,209
-
MMBtu
|
|
TOTAL RECOMMENDED | $277,484 | $1,270,836 |
$453,981
5,221,864
kWh
|
$(-221,706.0)
-
MMBtu
|
$45,209
-
MMBtu
|
||
TOTAL IMPLEMENTED | $13,941 | $10,836 |
$13,941
160,316
kWh
|
- | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs