Assessment Year | 1994 |
---|---|
Principal Product | Reagents for Medical Applications |
NAICS |
n/a
|
SIC | 2835: In Vitro and In Vivo Diagnostic Substances |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
250,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 2,350
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $577,378 | 6,458,382 |
kWh
|
$0.089 |
Natural Gas | $10,433 | 1,861 |
MMBtu
|
$5.61 |
Fuel Oil #2 | $103,580 | 25,796 |
MMBtu
|
$4.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $309,403 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,225 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,135 | $18,875 |
$8,135
91,442
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,374 | $9,484 |
$2,374
26,671
kWh
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $716 | $2,035 |
$716
7,913
kWh
|
- | - | |
04 | 2.7229: Air condition only space necessary | $76,210 | - |
$76,210
852,579
kWh
|
- | - | |
05 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $221,968 | $1,440,000 |
$438,169
4,901,524
kWh
|
$(-108,331.0)
-
MMBtu
|
$(-107,870.0) | |
TOTAL RECOMMENDED | $309,403 | $1,470,394 |
$525,604
5,880,129
kWh
|
$(-108,331.0)
-
MMBtu
|
$(-107,870.0) | ||
TOTAL IMPLEMENTED | $11,225 | $30,394 |
$11,225
126,026
kWh
|
- | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs