| Assessment Year | 2026 |
|---|---|
| Principal Product | Hospitality and Healthcare Textiles |
| NAICS | 313210: Broadwoven Fabric Mills |
| SIC | 2211: Broadwoven Fabric Mills, Cotton |
| Sales Range | $10 M to 50M |
| # of Employees | 114 |
| Plant Area |
400,000
ft2
|
| Annual Production | 14,947,500
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,559,810 | 20,632,913 |
kWh
|
$0.076 |
| Natural Gas | $60,219 | 11,928 |
MMBtu
|
$5.05 |
| TOTAL YEARLY COSTS | $1,620,029 | |||
| RECOMMENDED SAVINGS* | $1,000,273 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $12,911 | $100 |
$12,911
169,876
kWh
|
- | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $145,807 | $1,850 |
$148,707
1,956,672
kWh
|
- | $(-2,900.0) | - | |
| 03 | 2.2694: Use highest temperature for chilling or cold storage | $3,999 | $200 |
$3,999
52,616
kWh
|
- | - | - | |
| 04 | 2.4239: Eliminate or reduce compressed air usage | $17,554 | $900 |
$17,554
230,978
kWh
|
- | - | - | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $1,645 | $1,000 |
$1,485
19,548
kWh
|
$160
-
MMBtu
|
- | - | |
| 06 | 2.7135: Install occupancy sensors | $10,382 | $11,470 |
$10,382
136,608
kWh
|
- | - | - | |
| 07 | 2.4321: Upgrade obsolete equipment | $556,343 | $675,000 |
$221,295
2,911,776
kWh
|
$6,163
-
MMBtu
|
$168,000 | $160,885 | |
| 08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,701 | $25,000 |
$9,701
127,641
kWh
|
- | - | - | |
| 09 | 2.6212: Turn off equipment during breaks, reduce operating time | $156 | $567 |
$156
2,053
kWh
|
- | - | - | |
| 10 | 2.3413: Burn fossil fuel to produce steam to drive a steam turbine-generator and use steam exhaust for heat | $94,207 | $517,500 |
$123,500
1,625,000
kWh
|
$(-29,293.0)
-
MMBtu
|
- | - | |
| 11 | 2.9114: Use solar heat to make electricty | $147,568 | $1,244,837 |
$147,568
1,952,007
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $1,000,273 | $2,478,424 |
$697,258
9,184,775
kWh
|
$(-22,970.0)
-
MMBtu
|
$165,100 | $160,885 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs