| Assessment Year | 2026 |
|---|---|
| Principal Product | None |
| NAICS | 561210: Facilities Support Services |
| SIC | 8744: Facilities Support Management Services |
| Sales Range | less than $500 k |
| # of Employees | 300 |
| Plant Area |
271,170
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $202,396 | 4,375,336 |
kWh
|
$0.046 |
| Electricity Demand | $147,306 | 16,374 |
kW-mo/yr
|
$9.00 |
| Electricity Fees | $6,059 | - |
|
- |
| Fuel Oil #2 | $47,456 | 2,148 |
MMBtu
|
$22.09 |
| TOTAL YEARLY COSTS | $403,217 | |||
| RECOMMENDED SAVINGS* | $121,081 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 4.821: Pay bills on time to avoid late fees | $6,059 | $50 | - | - | $6,059 | - | |
| 02 | 2.7224: Reduce space conditioning during non-working hours | $11,999 | $5,850 |
$9,461
205,671
kWh
|
$2,538
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,809 | $15,278 |
$5,370
116,745
kWh
|
$1,439
-
kW-mo/yr
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $5,485 | $19,955 |
$4,326
94,050
kWh
|
$1,159
-
kW-mo/yr
|
- | - | |
| 05 | 2.1321: Replace fossil fuel equipment with electrical equipment | $8,013 | $91,000 |
$(-15,456.0)
(-336,000)
kWh
|
$(-12,096.0)
-
kW-mo/yr
|
- |
$35,565
-
MMBtu
|
|
| 06 | 2.7232: Replace existing hvac unit with high efficiency model | $33,339 | $501,250 |
$12,268
266,703
kWh
|
$3,289
-
kW-mo/yr
|
- |
$17,782
-
MMBtu
|
|
| 07 | 2.9114: Use solar heat to make electricty | $49,377 | $1,123,789 |
$39,981
863,811
kWh
|
$9,396
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $121,081 | $1,757,172 |
$55,950
1,210,980
kWh
|
$5,725
-
kW-mo/yr
|
$6,059 |
$53,347
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs