Assessment Year | 2024 |
---|---|
Principal Product | Refrigerators/Coolers |
NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
Sales Range | $10 M to 50M |
# of Employees | 55 |
Plant Area |
140,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $102,404 | 820,800 |
kWh
|
$0.12 |
TOTAL YEARLY COSTS | $102,404 | |||
RECOMMENDED SAVINGS* | $56,850 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,289 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,361 | $200 |
$1,361
10,891
kWh
|
- | |
02 | 2.6211: Conserve energy by efficient use of vending machines | $1,006 | $180 |
$1,006
8,051
kWh
|
- | |
03 | 2.6218: Turn off equipment when not in use | $2,209 | $400 |
$2,209
17,669
kWh
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,774 | $1,850 |
$8,674
69,390
kWh
|
$(-2,900.0) | |
05 | 2.6218: Turn off equipment when not in use | $5,870 | $2,400 |
$5,870
46,960
kWh
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,067 | $2,139 |
$2,067
16,533
kWh
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,466 | $6,640 |
$4,466
35,729
kWh
|
- | |
08 | 2.6218: Turn off equipment when not in use | $1,751 | $3,150 |
$1,751
14,009
kWh
|
- | |
09 | 2.9114: Use solar heat to make electricty | $32,346 | $469,616 |
$32,346
259,266
kWh
|
- | |
TOTAL RECOMMENDED | $56,850 | $486,575 |
$59,750
478,498
kWh
|
$(-2,900.0) | ||
TOTAL IMPLEMENTED | $21,289 | $16,379 |
$24,189
193,512
kWh
|
$(-2,900.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs