Assessment Year | 2020 |
---|---|
Principal Product | Plastic and Metal Fasteners and Assemblies |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $100 M to 500M |
# of Employees | 488 |
Plant Area |
245,000
ft2
|
Annual Production | 1,271,399,075
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,042,223 | 15,781,670 |
kWh
|
$0.066 |
Natural Gas | $52,350 | 11,210 |
MMBtu
|
$4.67 |
TOTAL YEARLY COSTS | $1,094,574 | |||
RECOMMENDED SAVINGS* | $185,123 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $66,111 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $39,291 | $1,575 |
$60,091
910,466
kWh
|
- | - | $(-20,800.0) | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,333 | $300 |
$2,333
35,348
kWh
|
- | - | - | |
03 | 2.8121: Apply for tax-free status for energy purchases | $13,180 | $2,000 | - | $13,180 | - | - | |
04 | 2.2511: Insulate bare equipment | $5,988 | $1,504 | - | - |
$5,988
-
MMBtu
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,540 | $995 |
$1,540
23,333
kWh
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,320 | $23,111 |
$5,320
80,599
kWh
|
- | - | - | |
07 | 2.9114: Use solar heat to make electricty | $117,472 | $845,798 |
$117,472
1,789,661
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $185,123 | $875,283 |
$186,755
2,839,407
kWh
|
$13,180 |
$5,988
-
MMBtu
|
$(-20,800.0) | ||
TOTAL IMPLEMENTED | $66,111 | $28,490 |
$67,743
1,026,413
kWh
|
$13,180 |
$5,988
-
MMBtu
|
$(-20,800.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs