Assessment Year | 2019 |
---|---|
Principal Product | RTV, Compact Tractor, Zero-Turn Mower |
NAICS | 333111: Farm Machinery and Equipment Manufacturing |
SIC | 3523: Farm Machinery and Equipment |
Sales Range | greater than $500 M |
# of Employees | 2,000 |
Plant Area |
1,179,000
ft2
|
Annual Production | 120,894
pieces
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,362,220 | 41,456,468 |
kWh
|
$0.057 |
Natural Gas | $1,073,277 | 203,385 |
MMBtu
|
$5.28 |
TOTAL YEARLY COSTS | $3,435,497 | |||
RECOMMENDED SAVINGS* | $218,412 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,479 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,068 | $3,500 |
$16,068
281,901
kWh
|
- | |
02 | 2.2511: Insulate bare equipment | $7,338 | $6,225 | - |
$7,338
-
MMBtu
|
|
03 | 2.7135: Install occupancy sensors | $5,577 | $13,969 |
$5,577
97,843
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,833 | $79,937 |
$14,833
260,235
kWh
|
- | |
05 | 2.3417: Use waste heat with a closed-cycle gas turbine-generator set to cogenerate electricity and heat | $174,595 | $1,725,000 |
$299,250
5,250,000
kWh
|
$(-124,654.9)
-
MMBtu
|
|
TOTAL RECOMMENDED | $218,412 | $1,828,630 |
$335,729
5,889,979
kWh
|
$(-117,316.6)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $36,479 | $97,405 |
$36,479
639,979
kWh
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs