| Assessment Year | 2017 |
|---|---|
| Principal Product | Plastic bottles |
| NAICS | 326160: Plastics Bottle Manufacturing |
| SIC | 3085: Plastics Bottles |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
150,000
ft2
|
| Annual Production | 21,524,177
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,258,030 | 13,626,880 |
kWh
|
$0.092 | |
| Waste Disposal Costs | |||||
| Water Usage | $45,891 | 5,629 |
Tgal
|
$8.15 | |
| TOTAL YEARLY COSTS | $1,303,921 | ||||
| RECOMMENDED SAVINGS* | $218,318 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $27,404 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,227 | $1,200 |
$3,227
35,078
kWh
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,228 | $13,889 |
$23,228
252,479
kWh
|
|
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $949 | $1,754 |
$949
10,314
kWh
|
|
| 04 | 2.2511: Insulate bare equipment | $149 | $304 |
$149
1,620
kWh
|
|
| 05 | 2.9114: Use solar heat to make electricty | $190,765 | $2,426,160 |
$190,765
2,066,361
kWh
|
|
| TOTAL RECOMMENDED | $218,318 | $2,443,307 |
$218,318
2,365,852
kWh
|
||
| TOTAL IMPLEMENTED | $27,404 | $16,843 |
$27,404
297,871
kWh
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs