Assessment Year | 2017 |
---|---|
Principal Product | Pharmaceuticals |
NAICS | 325414: Biological Product (except Diagnostic) Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $100 M to 500M |
# of Employees | 300 |
Plant Area |
200,000
ft2
|
Annual Production | 7,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $862,135 | 10,998,466 |
kWh
|
$0.078 | |
Natural Gas | $126,262 | 32,205 |
MMBtu
|
$3.92 | |
Waste Disposal Costs | |||||
Water Usage | $2,726 | 180 |
Tgal
|
$15.13 | |
TOTAL YEARLY COSTS | $991,123 | ||||
RECOMMENDED SAVINGS* | $127,829 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $18,871 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $15,852 | $90,000 |
$15,852
203,225
kWh
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,487 | $3,000 | - |
$1,487
-
MMBtu
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,122 | $35,484 |
$16,122
206,694
kWh
|
- | |
04 | 2.7135: Install occupancy sensors | $438 | $300 |
$438
5,619
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,749 | $6,180 |
$2,749
35,240
kWh
|
- | |
06 | 2.9114: Use solar heat to make electricty | $91,181 | $355,605 |
$91,181
1,168,984
kWh
|
- | |
TOTAL RECOMMENDED | $127,829 | $490,569 |
$126,342
1,619,762
kWh
|
$1,487
-
MMBtu
|
||
TOTAL IMPLEMENTED | $18,871 | $41,664 |
$18,871
241,934
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs