Assessment Year | 2011 |
---|---|
Principal Product | Nickel Cadmium Batteries |
NAICS | 335911: Storage Battery Manufacturing |
SIC | 3691: Storage Batteries |
Sales Range | $50 M to 100M |
# of Employees | 220 |
Plant Area |
206,000
ft2
|
Annual Production | 11,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $786,132 | 12,355,038 |
kWh
|
$0.064 |
Electricity Fees | $93,641 | - |
|
- |
Natural Gas | $217,713 | 65,741 |
MMBtu
|
$3.31 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $413,588 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $45,254 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,235 | $1 |
$6,235
84,510
kWh
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,458 | $56,350 |
$15,458
209,509
kWh
|
|
03 | 2.7135: Install occupancy sensors | $3,260 | $4,050 |
$3,260
44,189
kWh
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $45,254 | $2,500 |
$45,254
613,200
kWh
|
|
05 | 2.7313: Recycle air for heating, ventilation and air conditioning | $4,339 | $8,740 |
$4,339
58,806
kWh
|
|
06 | 2.2622: Replace existing chiller with high efficiency model | $339,042 | $1,340,000 |
$339,042
4,595,315
kWh
|
|
TOTAL RECOMMENDED | $413,588 | $1,411,641 |
$413,588
5,605,530
kWh
|
||
TOTAL IMPLEMENTED | $45,254 | $2,500 |
$45,254
613,200
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs