Assessment Year | 2006 |
---|---|
Principal Product | Frozen Food |
NAICS | 311412: Frozen Specialty Food Manufacturing |
SIC | 2038: Frozen Specialties, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 290 |
Plant Area |
208,000
ft2
|
Annual Production | 95,000,000
pieces
|
Production Hrs. Annual | 6,864
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,578,449 | 28,142,440 |
kWh
|
$0.056 |
Electricity Demand | $430 | 27 |
kW-mo/yr
|
$15.93 |
Electricity Fees | $91 | - |
|
- |
Natural Gas | $605,892 | 49,247 |
MMBtu
|
$12.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $166,975 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $100,548 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,160 | $1,250 |
$12,160
196
kWh
|
- | - | |
02 | 2.4314: Use synthetic lubricant | $6,843 | - |
$6,843
110,542
kWh
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,559 | $45,000 |
$14,559
235,210
kWh
|
- | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $21,105 | - | - |
$22,755
-
MMBtu
|
$(-1,650.0) | |
05 | 2.8112: Combine utility meters | $7,574 | $14,018 | - | - | $7,574 | |
06 | 2.2425: Use flue gases to heat process or service water | $40,180 | $30,000 | - |
$40,180
-
MMBtu
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $43,862 | $20,449 |
$43,862
708,600
kWh
|
- | - | |
08 | 2.8114: Change rate schedules or other changes in utility service | $11,830 | $36,750 | - | - | $11,830 | |
09 | 2.4133: Use most efficient type of electric motors | $8,862 | $47,168 |
$8,862
143,162
kWh
|
- | - | |
TOTAL RECOMMENDED | $166,975 | $194,635 |
$86,286
1,197,710
kWh
|
$62,935
-
MMBtu
|
$17,754 | ||
TOTAL IMPLEMENTED | $100,548 | $113,867 |
$79,443
1,087,168
kWh
|
$22,755
-
MMBtu
|
$(-1,650.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs