Assessment Year 2006
Principal Product dome structures
NAICS 332311: Prefabricated Metal Building and Component Manufacturing
SIC 3448: Prefabricated Metal Buildings and Components
Sales Range $10
M
to 50
M
# of Employees 53
Plant Area 95,000
ft2
Annual Production 200
pieces
Production Hrs. Annual 4,000
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $98,587 1,886,523
kWh
Electricity Demand $26,670 2,610
kW-mo/yr
Electricity Fees $25,535 -
Natural Gas $55,299 2,562
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $23,206 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,555

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.8114: Change rate schedules or other changes in utility service $8,555 - - - $8,555
02 2.8114: Change rate schedules or other changes in utility service $3,095 $13,342 - - $3,095
03 2.7135: Install occupancy sensors $454 $280 $454
8,702
kWh
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $7,167 $23,331 $4,617
88,358
kWh
$2,550
-
kW-mo/yr
-
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $746 $400 $470
8,993
kWh
$276
-
kW-mo/yr
-
06 2.8112: Combine utility meters $2,907 $7,120 - - $2,907
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $282 $234 $140
2,672
kWh
$142
-
kW-mo/yr
-
TOTAL RECOMMENDED $23,206 $44,707 $5,681
108,725
kWh
$2,968
-
kW-mo/yr
$14,557
TOTAL IMPLEMENTED $8,555 - - - $8,555
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs