Assessment Year 2005
Principal Product News Papers
NAICS 511110: Newspaper Publishers
SIC 2711: Newspapers: Publishing, or Publishing and Printing
Sales Range $50
M
to 100
M
# of Employees 450
Plant Area 125,000
ft2
Annual Production 67,100,000
pieces
Production Hrs. Annual 8,760
hrs
Location (State) Tennessee

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $183,034 4,750,400
kWh
Electricity Demand $85,626 9,170
kW-mo/yr
Electricity Fees $228 -
Natural Gas $35,457 3,440
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $29,889 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $11,507

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $8,729 $25,590 $5,826
162,099
kWh
$2,903
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $719 $663 $522
14,530
kWh
$197
-
kW-mo/yr
-
03 2.7135: Install occupancy sensors $1,135 $543 $1,135
31,583
kWh
- -
04 2.7124: Make a practice of turning off lights when not needed $427 $120 $236
6,570
kWh
$191
-
kW-mo/yr
-
05 2.8112: Combine utility meters $3,880 $8,000 - - $3,880
06 2.7224: Reduce space conditioning during non-working hours $1,540 $1,120 $1,540
42,854
kWh
- -
07 3.4155: Meter waste water $7,200 $550 - - $7,200
08 2.7232: Replace existing hvac unit with high efficiency model $497 $1,300 $497
13,840
kWh
- -
09 2.7232: Replace existing hvac unit with high efficiency model $5,762 $50,525 $5,046
140,410
kWh
$716
-
kW-mo/yr
-
TOTAL RECOMMENDED $29,889 $88,411 $14,802
411,886
kWh
$4,007
-
kW-mo/yr
$11,080
TOTAL IMPLEMENTED $11,507 $28,216 $8,216
228,622
kWh
$3,291
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs