| Assessment Year | 2005 |
|---|---|
| Principal Product | News Papers |
| NAICS | 511110: Newspaper Publishers |
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $50 M to 100M |
| # of Employees | 450 |
| Plant Area |
125,000
ft2
|
| Annual Production | 67,100,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $183,034 | 4,750,400 |
kWh
|
$0.039 |
| Electricity Demand | $85,626 | 9,170 |
kW-mo/yr
|
$9.34 |
| Electricity Fees | $228 | - |
|
- |
| Natural Gas | $35,457 | 3,440 |
MMBtu
|
$10.31 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,889 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,507 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,729 | $25,590 |
$5,826
162,099
kWh
|
$2,903
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $719 | $663 |
$522
14,530
kWh
|
$197
-
kW-mo/yr
|
- | |
| 03 | 2.7135: Install occupancy sensors | $1,135 | $543 |
$1,135
31,583
kWh
|
- | - | |
| 04 | 2.7124: Make a practice of turning off lights when not needed | $427 | $120 |
$236
6,570
kWh
|
$191
-
kW-mo/yr
|
- | |
| 05 | 2.8112: Combine utility meters | $3,880 | $8,000 | - | - | $3,880 | |
| 06 | 2.7224: Reduce space conditioning during non-working hours | $1,540 | $1,120 |
$1,540
42,854
kWh
|
- | - | |
| 07 | 3.4155: Meter waste water | $7,200 | $550 | - | - | $7,200 | |
| 08 | 2.7232: Replace existing hvac unit with high efficiency model | $497 | $1,300 |
$497
13,840
kWh
|
- | - | |
| 09 | 2.7232: Replace existing hvac unit with high efficiency model | $5,762 | $50,525 |
$5,046
140,410
kWh
|
$716
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $29,889 | $88,411 |
$14,802
411,886
kWh
|
$4,007
-
kW-mo/yr
|
$11,080 | ||
| TOTAL IMPLEMENTED | $11,507 | $28,216 |
$8,216
228,622
kWh
|
$3,291
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs