| Assessment Year | 2005 |
|---|---|
| Principal Product | Plastic Film |
| NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
| SIC | 3081: Unsupported Plastics Film and Sheet |
| Sales Range | $50 M to 100M |
| # of Employees | 92 |
| Plant Area |
125,000
ft2
|
| Annual Production | 35,000,000
lb
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $458,658 | 21,925,000 |
kWh
|
$0.021 |
| Electricity Demand | $581,530 | 50,573 |
kW-mo/yr
|
$11.50 |
| Electricity Fees | $81,069 | - |
|
- |
| Natural Gas | $61,057 | 5,505 |
MMBtu
|
$11.09 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $86,747 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $47,987 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,040 | $32,725 |
$6,450
230,465
kWh
|
$5,590
-
kW-mo/yr
|
- | - | |
| 02 | 2.7134: Use photocell controls | $7,520 | $32,480 |
$5,840
208,716
kWh
|
$1,680
-
kW-mo/yr
|
- | - | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $72 | - |
$5
178
kWh
|
- | - |
$67
-
MMBtu
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $775 | $500 |
$491
17,540
kWh
|
$284
-
kW-mo/yr
|
- | - | |
| 05 | 2.6218: Turn off equipment when not in use | $2,820 | $500 |
$1,750
62,455
kWh
|
$1,070
-
kW-mo/yr
|
- | - | |
| 06 | 2.2628: Utilize a less expensive cooling method | $1,780 | $7,500 |
$1,780
63,453
kWh
|
- | - | - | |
| 07 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $35,100 | $15,000 | - |
$35,100
-
kW-mo/yr
|
- | - | |
| 08 | 2.7232: Replace existing hvac unit with high efficiency model | $11,320 | $10,000 |
$5,490
152,627
kWh
|
$5,830
-
kW-mo/yr
|
- | - | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,950 | $6,600 |
$2,950
81,850
kWh
|
- | - | - | |
| 10 | 2.8112: Combine utility meters | $12,370 | - | - | - | $12,370 | - | |
| TOTAL RECOMMENDED | $86,747 | $105,305 |
$24,756
817,284
kWh
|
$49,554
-
kW-mo/yr
|
$12,370 |
$67
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $47,987 | $48,225 |
$6,946
248,183
kWh
|
$40,974
-
kW-mo/yr
|
- |
$67
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs