Assessment Year 2005
Principal Product Heating Elements
NAICS 335210: Small Electrical Appliance Manufacturing
SIC 3634: Electric Housewares and Fans
Sales Range $10
M
to 50
M
# of Employees 156
Plant Area 125,000
ft2
Annual Production 4,200,000
pieces
Production Hrs. Annual 6,000
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $163,079 4,032,976
kWh
Electricity Demand $109,146 8,973
kW-mo/yr
Electricity Fees $4,814 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $40,496 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $17,764

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $7,607 $4,928 $4,153
110,746
kWh
$3,454
-
kW-mo/yr
- -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $3,418 $2,172 $1,868
49,800
kWh
$1,550
-
kW-mo/yr
- -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $1,342 $990 $230
6,132
kWh
$131
-
kW-mo/yr
- $981
04 2.7135: Install occupancy sensors $1,633 $400 $1,633
30,309
kWh
- - -
05 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle $14,902 $2,757 $394
10,497
kWh
$6,208
-
kW-mo/yr
$8,300
-
MMBtu
-
06 2.6242: Minimize operation of equipment maintained in standby condition $4,855 - - $4,855
-
kW-mo/yr
- -
07 2.6242: Minimize operation of equipment maintained in standby condition $6,739 - - $6,739
-
kW-mo/yr
- -
TOTAL RECOMMENDED $40,496 $11,247 $8,278
207,484
kWh
$22,937
-
kW-mo/yr
$8,300
-
MMBtu
$981
TOTAL IMPLEMENTED $17,764 $7,100 $6,021
160,546
kWh
$11,743
-
kW-mo/yr
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs