Assessment Year | 2004 |
---|---|
Principal Product | Door Mats |
NAICS | 314110: Carpet and Rug Mills |
SIC | 2273: Carpets and Rugs |
Sales Range | $10 M to 50M |
# of Employees | 61 |
Plant Area |
88,075
ft2
|
Annual Production | 11,057
thousand feet
|
Production Hrs. Annual | 4,650
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $45,602 | 1,753,920 |
kWh
|
$0.026 |
Electricity Demand | $71,699 | 4,922 |
kW-mo/yr
|
$14.57 |
Electricity Fees | $16,307 | - |
|
- |
Natural Gas | $91,886 | 13,052 |
MMBtu
|
$7.04 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,962 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,781 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8112: Combine utility meters | $4,508 | $9,000 | - | - | - | $4,508 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $895 | $200 |
$373
14,334
kWh
|
$522
-
kW-mo/yr
|
- | - | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $835 | - |
$152
5,838
kWh
|
- |
$683
-
MMBtu
|
- | |
04 | 2.7221: Lower temperature during the winter season and vice-versa | $815 | $500 |
$548
21,110
kWh
|
- |
$267
-
MMBtu
|
- | |
05 | 2.1113: Reduce combustion air flow to optimum | $8,427 | $1,750 | - | - |
$8,427
-
MMBtu
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,639 | $9,925 |
$2,823
108,610
kWh
|
$2,816
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,051 | $50,551 |
$3,781
145,406
kWh
|
$4,270
-
kW-mo/yr
|
- | - | |
08 | 2.7313: Recycle air for heating, ventilation and air conditioning | $792 | $1,910 | - | - |
$792
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $29,962 | $73,836 |
$7,677
295,298
kWh
|
$7,608
-
kW-mo/yr
|
$10,169
-
MMBtu
|
$4,508 | ||
TOTAL IMPLEMENTED | $9,781 | $50,751 |
$4,306
165,578
kWh
|
$4,792
-
kW-mo/yr
|
$683
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs