Assessment Year | 2003 |
---|---|
Principal Product | SOFT DRINKS |
NAICS | 312111: Soft Drink Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | n/a |
# of Employees | 263 |
Plant Area |
300,000
ft2
|
Annual Production | 44,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $377,752 | 16,344,387 |
kWh
|
$0.023 |
Electricity Demand | $458,867 | 35,442 |
kW-mo/yr
|
$12.95 |
Natural Gas | $278,228 | 44,393 |
MMBtu
|
$6.27 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $143,273 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $14,388 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,490 | $6,340 |
$4,320
186,950
kWh
|
$3,170
-
kW-mo/yr
|
- | - | - | |
02 | 2.2511: Insulate bare equipment | $354 | $248 | - | - | - |
$354
-
MMBtu
|
- | |
03 | 2.6218: Turn off equipment when not in use | $5,848 | - |
$3,372
145,891
kWh
|
$2,476
-
kW-mo/yr
|
- | - | - | |
04 | 2.8112: Combine utility meters | $113,960 | - | - | - | $113,960 | - | - | |
05 | 3.4115: Recover and reuse cooling water | $13,569 | $12,000 | n/a |
$(-13,395.0)
(-218,429)
kWh
|
- | - | - |
$26,964
-
Tgal
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,050 | $300 |
$605
26,166
kWh
|
$445
-
kW-mo/yr
|
- | - | - | |
07 | 2.7135: Install occupancy sensors | $130 | $50 |
$130
3,762
kWh
|
- | - | - | - | |
08 | 2.9113: Use solar heat for heat | $872 | $490 |
$872
37,720
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $143,273 | $19,428 |
$(-4,096.0)
182,060
kWh
|
$6,091
-
kW-mo/yr
|
$113,960 |
$354
-
MMBtu
|
$26,964
-
Tgal
|
||
TOTAL IMPLEMENTED | $14,388 | $6,640 |
$8,297
359,007
kWh
|
$6,091
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs