| Assessment Year | 2003 |
|---|---|
| Principal Product | WOVEN CLOTH |
| NAICS | 313210: Broadwoven Fabric Mills |
| SIC | 2211: Broadwoven Fabric Mills, Cotton |
| Sales Range | $100 M to 500M |
| # of Employees | 400 |
| Plant Area |
500,000
ft2
|
| Annual Production | 225,000,000
thousand feet
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,565,989 | 60,153,000 |
kWh
|
$0.043 |
| Natural Gas | $2,743,914 | 567,498 |
MMBtu
|
$4.84 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $267,573 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $53,617 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $770 | $500 |
$770
23,754
kWh
|
- | |
| 02 | 2.7124: Make a practice of turning off lights when not needed | $30,090 | $6,864 |
$30,090
581,244
kWh
|
- | |
| 03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $32,869 | $500 | - |
$32,869
-
MMBtu
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,159 | $6,250 |
$11,159
324,942
kWh
|
- | |
| 05 | 2.2135: Repair and eliminate steam leaks | $5,000 | $1,000 | - |
$5,000
-
MMBtu
|
|
| 06 | 2.2511: Insulate bare equipment | $3,238 | $386 | - |
$3,238
-
MMBtu
|
|
| 07 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $108,981 | $44,500 | - |
$108,981
-
MMBtu
|
|
| 08 | 2.4133: Use most efficient type of electric motors | $4,589 | $49,906 |
$4,589
141,633
kWh
|
- | |
| 09 | 2.4322: Use or replace with energy efficient substitutes | $70,877 | $80,650 | - |
$70,877
-
MMBtu
|
|
| TOTAL RECOMMENDED | $267,573 | $190,556 |
$46,608
1,071,573
kWh
|
$220,965
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $53,617 | $57,656 |
$15,748
466,575
kWh
|
$37,869
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs