Assessment Year | 2003 |
---|---|
Principal Product | BAKERY GOODS |
NAICS | 311821: Cookie and Cracker Manufacturing |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $50 M to 100M |
# of Employees | 382 |
Plant Area |
51,363,918
ft2
|
Annual Production | 41,999,871
lb
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $619,064 | 11,664,798 |
kWh
|
$0.053 |
Natural Gas | $202,200 | 60,370 |
MMBtu
|
$3.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $361,675 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3132: Recharge batteries on during off-peak demand periods | $233 | - | n/a |
$233
18,304
kWh
|
- | - | - | - |
02 | 2.6218: Turn off equipment when not in use | $27,457 | - | n/a |
$27,457
893,200
kWh
|
- | - | - | - |
03 | 2.8118: Check for accuracy of utility / power meters | $21,000 | $8,220 | n/a | - | - | - | - | $21,000 |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $64,596 | $238,800 | n/a |
$35,412
1,018,368
kWh
|
$29,184
-
kW-mo/yr
|
- | - | - |
05 | 2.7124: Make a practice of turning off lights when not needed | $3,035 | - | n/a |
$3,035
87,279
kWh
|
- | - | - | - |
06 | 2.1113: Reduce combustion air flow to optimum | $3,160 | - | n/a | - | - |
$5,660
-
MMBtu
|
$(-2,500.0) | - |
07 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $200,750 | $814,000 | n/a |
$253,700
3,000,000
kWh
|
- |
$(-52,950.0)
-
MMBtu
|
- | - |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $41,444 | $500 | n/a |
$30,715
762,551
kWh
|
$10,729
-
kW-mo/yr
|
- | - | - |
TOTAL RECOMMENDED | $361,675 | $1,061,520 |
$350,552
5,779,702
kWh
|
$39,913
-
kW-mo/yr
|
$(-47,290.0)
-
MMBtu
|
$(-2,500.0) | $21,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs