Assessment Year 2003
Principal Product PRESSURE GAUGES
NAICS 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial
SIC 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products
Sales Range $50
M
to 100
M
# of Employees 466
Plant Area 240,000
ft2
Annual Production 7,000,000
pieces
Production Hrs. Annual 6,240
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $291,926 5,713,181
kWh
Natural Gas $43,881 3,536
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $93,870 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,222

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Administrative Changes Savings Water Consumption Savings
01 2.2511: Insulate bare equipment $1,646 $264 $1,646
56,784
kWh
- -
02 2.8112: Combine utility meters $996 - - $996 -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,387 $5,000 $1,387
80,496
kWh
- -
04 2.4239: Eliminate or reduce compressed air usage $1,711 - $1,711
59,030
kWh
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $6,124 $12,499 $6,124
193,974
kWh
- -
06 2.7111: Reduce illumination to minimum necessary levels $8,513 $350 $8,513
229,600
kWh
- -
07 2.4231: Reduce the pressure of compressed air to the minimum required $7,644 $10,000 $7,644
263,603
kWh
- -
08 2.7292: Lower ceiling to reduce conditioned space $22,273 $8,000 $22,273
618,700
kWh
- -
09 3.4111: Use closed cycle process to minimize waste water production $43,576 $51,000 n/a - - $43,576
-
Tgal
TOTAL RECOMMENDED $93,870 $87,113 $49,298
1,502,187
kWh
$996 $43,576
-
Tgal
TOTAL IMPLEMENTED $9,222 $17,499 $9,222
333,500
kWh
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Administrative Changes Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs