Assessment Year 2002
Principal Product Rug Yarns
NAICS
n/a
SIC 2282: Yarn Texturizing, Throwing, Twisting, and Winding Mills
Sales Range $10
M
to 50
M
# of Employees 123
Plant Area 104,360
ft2
Annual Production 21,800,000
lb
Production Hrs. Annual 8,000
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $271,505 12,687,600
kWh
Electricity Demand $320,870 2,092
kW-mo/yr
Electricity Fees $24,682 -
Natural Gas $129,544 21,762
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $41,644 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $14,888

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.2622: Replace existing chiller with high efficiency model $19,440 $122,500 $1,190
151,800
kWh
$18,250
-
kW-mo/yr
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,592 $1,900 $330
42,000
kWh
$1,262
-
kW-mo/yr
03 2.4133: Use most efficient type of electric motors $6,450 $50,177 $1,334
169,695
kWh
$5,116
-
kW-mo/yr
04 2.7142: Utilize higher efficiency lamps and/or ballasts $186 $16,560 $139
17,650
kWh
$47
-
kW-mo/yr
05 2.4239: Eliminate or reduce compressed air usage $2,700 $300 $2,700
219,200
kWh
-
06 2.4231: Reduce the pressure of compressed air to the minimum required $7,130 $7,000 $1,478
188,000
kWh
$5,652
-
kW-mo/yr
07 2.4224: Upgrade controls on compressors $3,488 - $723
92,000
kWh
$2,765
-
kW-mo/yr
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $658 $500 $136
1,083
kWh
$522
-
kW-mo/yr
TOTAL RECOMMENDED $41,644 $198,937 $8,030
881,428
kWh
$33,614
-
kW-mo/yr
TOTAL IMPLEMENTED $14,888 $52,877 $5,223
523,978
kWh
$9,665
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs