Assessment Year | 2002 |
---|---|
Principal Product | Rug Yarns |
NAICS |
n/a
|
SIC | 2282: Yarn Texturizing, Throwing, Twisting, and Winding Mills |
Sales Range | $10 M to 50M |
# of Employees | 123 |
Plant Area |
104,360
ft2
|
Annual Production | 21,800,000
lb
|
Production Hrs. Annual | 8,000
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $271,505 | 12,687,600 |
kWh
|
$0.021 |
Electricity Demand | $320,870 | 2,092 |
kW-mo/yr
|
$153.38 |
Electricity Fees | $24,682 | - |
|
- |
Natural Gas | $129,544 | 21,762 |
MMBtu
|
$5.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $41,644 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $14,888 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.2622: Replace existing chiller with high efficiency model | $19,440 | $122,500 |
$1,190
151,800
kWh
|
$18,250
-
kW-mo/yr
|
|
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,592 | $1,900 |
$330
42,000
kWh
|
$1,262
-
kW-mo/yr
|
|
03 | 2.4133: Use most efficient type of electric motors | $6,450 | $50,177 |
$1,334
169,695
kWh
|
$5,116
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $186 | $16,560 |
$139
17,650
kWh
|
$47
-
kW-mo/yr
|
|
05 | 2.4239: Eliminate or reduce compressed air usage | $2,700 | $300 |
$2,700
219,200
kWh
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,130 | $7,000 |
$1,478
188,000
kWh
|
$5,652
-
kW-mo/yr
|
|
07 | 2.4224: Upgrade controls on compressors | $3,488 | - |
$723
92,000
kWh
|
$2,765
-
kW-mo/yr
|
|
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $658 | $500 |
$136
1,083
kWh
|
$522
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $41,644 | $198,937 |
$8,030
881,428
kWh
|
$33,614
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $14,888 | $52,877 |
$5,223
523,978
kWh
|
$9,665
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs