Assessment Year | 1997 |
---|---|
Principal Product | Chicken Broth |
NAICS |
n/a
|
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
70,000
ft2
|
Annual Production | 48,500,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $196,201 | 7,741,794 |
kWh
|
$0.025 |
Electricity Demand | $149,851 | 17,506 |
kW-mo/yr
|
$8.56 |
Electricity Fees | $9,078 | - |
|
- |
Natural Gas | $450,444 | 126,934 |
MMBtu
|
$3.55 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $127,501 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $114,531 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8113: Purchase gas directly from a contract gas supplier | $26,200 | $173,400 | - | - |
$(-37,150.0)
-
MMBtu
|
$63,350 | - | - | |
02 | 2.8112: Combine utility meters | $3,680 | $1,830 | - | - | - | $3,680 | - | - | |
03 | 2.3212: Optimize plant power factor | $22,150 | $24,500 | - |
$22,150
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7132: Install timers on light switches in little used areas | $2,488 | $400 |
$1,183
47,186
kWh
|
$1,305
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.2437: Recover waste heat from equipment | $9,290 | $13,500 | - | - |
$9,290
-
MMBtu
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $1,303 | $1,665 | - | - |
$1,303
-
MMBtu
|
- | - | - | |
07 | 2.2121: Increase amount of condensate returned | $14,110 | $850 | - | - |
$11,440
-
MMBtu
|
- | $2,670 | - | |
08 | 2.4133: Use most efficient type of electric motors | $7,850 | $49,700 |
$4,820
191,383
kWh
|
$3,030
-
kW-mo/yr
|
- | - | - | - | |
09 | 3.7141: Improve cleaning efficiency by maintaining cleaning system | $40,430 | $4,200 |
$1,450
58,030
kWh
|
$980
-
kW-mo/yr
|
- | - | - | $38,000 | |
TOTAL RECOMMENDED | $127,501 | $270,045 |
$7,453
296,599
kWh
|
$27,465
-
kW-mo/yr
|
$(-15,117.0)
-
MMBtu
|
$67,030 | $2,670 | $38,000 | ||
TOTAL IMPLEMENTED | $114,531 | $254,715 |
$7,453
296,599
kWh
|
$27,465
-
kW-mo/yr
|
$(-24,407.0)
-
MMBtu
|
$63,350 | $2,670 | $38,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs